Before starting the cooling
tower please follow the below procedure.
CLEANING:
Remove dirt and
trash accumulated in the hot water distribution basins. Clean clogged
nozzles. Use a water hose to flush out any sediment from cold water basins,
sump and screens.
OPERATE WATER SYSTEM:
Open all
hot water flow control valves. Start the circulating water pumps. Increase
the flow of circulating water gradually to design water rate to avoid surges
or water hammer which could damage the distribution piping or hot water
deck. Circulate water over the tower continuously for two days before
starting mechanical equipment and putting the tower into continuous
operation.
INSPECTION:
You must
inspect all operating assemblies before they are placed in operation. Please
follow the following inspection procedure before starting the tower.
1. Check tightness of
the following bolted joints in the fan and drive assemblies:
a.
Fan hub damp bolts.
b. Fan hub
cover bolts.
c. Gear
reducer and motor mounting bolts.
d. Drive
shaft coupling and guard bolts.
2. Rotate fan by hand
to be sure of free rotation and ample tip clearance.
3. Check motor
insulation.
4. Lubricate the motor
according to motor manufacturer’s instructions.
5. Test run each fan
separately for a short time. Check for excessive vibration or unusual noise.
Fan must rotate clockwise when viewed from above. Recheck gear reducer oil
level, when gear box is installed.
6. Check functioning
of make-up water supply.
7. Make sure the blow
down or bleed-off will carry the proper amount of water.
TOWER
STARTING PROCEDURE.
FILLING THE WATER SYSTEM:
Fill
the cold water basin and circulating water system until the operating water
level is reached. Completely open all hot water flow control valves, and
start circulating water pumps. Increase the flow of circulating water
gradually to avoid surges or water hammer which could damage the
distribution piping. adjust valves to equalize the hot water depth in the
distribution basin. Lock valves in desired open position with valve locking
bar.
Clean the sump screens
several times during the first weeks of operation. After this, clean sump
screen as required.
TOWER
OPERATIONS.
TOWER PERFORMANCE:
Keep the
tower clean and the water distribution uniform to obtain continued maximum
cooling capacity do not allow excessive deposits of scale or algae to build
up on the fills or Drift Eliminators. Keep the metering orifices free of
debris to assure correct distribution and cooling of water.
The capacity of tower
to cool water to a given cold water temperature varies with the wet bulb
temperature and the heat load on the tower. As the wet bulb temperature
drops, the cold water temperature also drops. However, the cold water
temperature does not drop as much as the wet bulb temperature.
Please remember, a
tower does not control the heat load. The quantity of the water circulated
determines the cooling range for a given heat load. The hot and cold water
temperature increases with higher heat loads.
COLD WATER
COLLECTING BASIN :
The normal water depth
in a concrete basin is 9 to 15 inches below the curve. Adjust the makeup
water supply to maintain this water level. Low operating depths of the water
require air baffles under the fill to prevent air bypass. Maintain
sufficient water depth to prevent cavitations.
HOT WATER
DISTRIBUTION SYSTEM :
Keep metering orifices
clean and in place in distribution basins. Adjust water flow to the same
depth in the distribution of all cells. Design water depth varies from 4” to
7” depending upon design circulating water rate. If a major change in the
quantity of water to be circulated over the tower is to be water break-up
and maintain the proper water level.
|