PROBLEM   CAUSE FOR THE PROBLEM  SOLUTION
Unusual fan drive Loose bolts and cap screws Tighten all bolts and cap screws on all mechanical equipment and supports.
     
Vibration / Noise Unbalanced drive shafts or worn couplings Make sure motor and gear reducer shafts are in proper alignment and “match marks” properly matched. Repair or replace worn couplings. Rebalancing cap screws. See drive shaft service manual.
 

Fan

Be sure blades are positioned in correct sockets. Check match numbers. Make certain all blades are as far from center of fan as safety devices permit. All blades must be pitched the same. See fan service manual. Clean off deposits buildup on blades.
 

Worm gear reducer bearings

Check fan and pinion shafts end play. Replace bearings as necessary.
 

Unbalanced motor

Disconnect load and operate motor. If motor still vibrates, rebalance rotor.
 

Bent gear reducer shaft

Check fan and pinion shafts with dial indicator. Replace if necessary.
 

Bearing damaged

Check motor/gearbox.

  Fan blades defective Replace fan.
 

Weak Structure

Repair Tower.

 

Drive shaft Problem

Repair, balance.
     
Fan Noise

Loose fan hub cover

Tighten hub cover fasteners.

 

Blade rubbing inside fan cylinder

Adjust cylinder to provide blade tip clearance.
  Loose bolts in blade clamps Check and tighten if necessary.
     
Cold Temperature not achieved

Fan not running

Start Fan.
 

Water quantity more

Check the flow.

 

Nozzles Blocked

Clean nozzles.

 

Uneven water flow

Check flow valves.
  Tower in bad condition Call “ Melfrank”.
 

Air leakage/short circuit

Look for Voids/Gaps in sheeting, Fan Deck.
 

Fills choked/broken

Clean Fills.
     
Very high drift losses More water

Reduce the water flow.

 

Drift eliminators missing

Replace or correct.
  High CFM from fan Reduce CFM.
     

Water falling from Louver side

Too much water in circulation

Reduce water.

 

Nozzles Blocked

Clean/Replace nozzles.

 

Water overflowing

Drill more holes and fix nozzles.

  Louvers broken or mis fitted Replace louvers & fit properly.